Conditions:
No water, no oil - Pump will not run
Water only - Pump will start running at approximately 10"
and will run until water is below the lower probe (4").
Water and oil - Pump will start running at approximately 10"
of water and run until oil reaches the lower probe (4") and then stop; if water
continues to flow into the pit, the pump will run until the
oil reaches the lower probe.
Oil only - Pump will not run. If the oil level reaches approximately
12" the high oil/water alarm will sound.
High oil/water alarm -The high oil/water alarm will sound
if oil is present and the level in the pit reaches approximately
12" or if the water level in the pit reaches approximately
12" warning that the pump has failed.
WARNING:
The switch and pump are not rated for explosive environments.
This product is intended for hydraulic oils only.
|