Elevator Sump Oil Alarm System Specifications
System Overview
The Elevator Sump Oil Alarm System uses a Patented Dual Probe Capacitance Switch to differentiate between water and oil by measuring the dielectric of the medium at the sensor.
Controller Features:
-
Solid-state with NEMA 4X enclosure (suitable for elevator pit mounting).
-
High-liquid audible alarm.
-
Optional dry N.O. or N.C. contact for remote monitoring.
-
UL Listed #508A Type L, File #E187669.
Pump Features:
-
Oil-filled, hermetically sealed.
-
Automatic reset & thermal overload protection.
-
UL Listed #778 and CSA #108.
Installation:
-
Fully assembled, pre-calibrated, and tested before shipping.
-
Includes check valve and mounting hardware.
How to Choose the Correct System
Application | Head Feet | Part Number |
---|---|---|
Single elevator | ≤19’ | ESA 50/100 |
Single elevator | 19’–35’ | ESA 100/100 |
2 elevators (duplex) | ≤17’ | ESA 50/100HF |
2 elevators (duplex) | 14’6”–25’6” | ESA 100/100HF |
3 elevators (triplex) | ≤14’6” | ESA 100/100HF |
ESA 50/100
-
Pump: ½ HP
-
Application: Single elevator, up to 19’ head feet.
-
Flow Rate: 3,000 GPH (meets ASME A17.1-2007 code for one elevator).
-
Sump Pit Requirements:
-
Minimum 16″ diameter × 18″ depth (24″ ideal).
-
Poured-in-place: 16″ × 16″ × 18″–24″ deep to 24″ × 24″ × 24″ deep.
-
-
Operation:
-
Pump activates at 10″ water, stops at 4″.
-
Oil detection at 10″ triggers alarm (pump disabled).
-
High liquid alarm at 14″ (audible + optional remote contact).
-
-
Cut Sheet: ESA 50 100 Pump Curve (PDF)
ESA 100/100
-
Pump: ¾ HP
-
Application: Single elevator, 19’–35’ head feet.
-
Flow Rate: 3,000 GPH (meets ASME A17.1-2007 code for one elevator).
-
Sump Pit Requirements: Same as ESA 50/100.
-
Operation: Same as ESA 50/100.
-
Cut Sheet Link: [Insert Link Here]
ESA 50/100HF (Duplex System)
-
Pump: ¾ HP
-
Application: 2 elevators (duplex) in same shaft.
-
Up to 17’ head feet (or 15’–25’6″ for ESA 100/100HF).
-
-
Flow Rate: 6,000 GPH at 15’ head feet (meets code for 2 elevators).
-
Sump Pit Requirements:
-
Minimum 18″ diameter × 24″ depth (24″ × 24″ × 24″ ideal).
-
-
Operation:
-
Pump activates at 16″ water, stops at 10″.
-
Oil detection at 16″ triggers alarm (pump disabled).
-
High liquid alarm at 18″ (audible + optional remote contact).
-
-
Cut Sheet Link: [Insert Link Here]
ESA 100/100HF (Triplex System)
-
Pump: 1 HP
-
Application:
-
3 elevators (triplex) in same shaft (up to 14’6″ head feet).
-
2 elevators (duplex) with 14’6″–25’6″ head feet.
-
-
Flow Rate: 9,000 GPH at 14’6″ head feet (meets code for 3 elevators).
-
Sump Pit Requirements: Same as ESA 50/100HF.
-
Operation: Same as ESA 50/100HF.
-
Cut Sheet Link: [Insert Link Here]
Sequence of Operation
-
Water detected: Pump activates at specified level, deactivates at lower threshold.
-
Oil detected: Alarm triggers, pump disabled.
-
High liquid level (oil/water): Audible alarm + optional remote signal.
Notes:
-
All systems include check valve and mounting hardware.
-
Pumps are hermetically sealed and thermal overload protected.